Power supply TRIO 1 phase 12VDC, 10A, 120W

Power supply TRIO 1 phase 12VDC, 10A, 120W


Power supply 12VDC with DIN rail mounting is robust, compact and efficient source, specialized on industrial automation systems. Input: 1x phase, output 12V DC, 10A. More

Manufacturer: PHOENIX CONTACT Code: 2866488

162 EUR excl. VAT (196,02 EUR incl. VAT)
In stock
pcs

Power supply 12VDC with DIN rail mounting is robust, compact and efficient source, specialized on industrial automation systems. Input: 1x phase, output 12V DC, 10A. More

Manufacturer: PHOENIX CONTACT Code: 2866488

TRIO POWER power supplies with standard functionality
TRIO POWER is particularly suited to standard machine production, thanks to 1- and 3-phase versions up to 960 W. The wide-range input and the international approval package enable worldwide use.
The robust metal housing, the high electric strength, and the wide temperature range ensure a high level of power supply reliability.

  • Use the third negative terminal block as a grounding terminal block and minimize installation costs
  • Rugged design with metal housing and wide temperature range from -25 to +70°C
  • Maximum operational reliability thanks to high MTBF (mean time between failures) of more than 500,000 hours and high dielectric strength of up to 300 V AC
  • Compensation of voltage drops by means of output voltage that can be adjusted on the front

Dimensions

Width 40 mm
Height 130 mm
Depth 115 mm

Ambient conditions

Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 55° C derating : 2.5%/K)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Climatic class 3K3 (in acc. with EN 60721)
Degree of pollution 2

Input data

Nominal input voltage range 100 V AC ... 240 V AC
Input voltage range 85 V AC ... 264 V AC (derating < 90 V AC: 2.5 % per Kelvin)
Dielectric strength maximum 300 V AC
AC frequency range 45 Hz ... 65 Hz
Discharge current to PE < 3.5 mA
Current consumption 1.7 A (120 V AC)
0.9 A (230 V AC)
Nominal power consumption 218.7 VA
Inrush current < 15 A
Mains buffering time > 20 ms (120 V AC)
> 86 ms (230 V AC)
Recommended breaker for input protection 6 A ... 16 A (Characteristics B, C, D, K)
Power factor (cos phi) 0.63
Type of protection Transient surge protection
Protective circuit/component Varistor

Output data

Nominal output voltage 12 V DC ±1 %
Setting range of the output voltage (USet) 10 V DC ... 18 V DC (> 12 V DC, constant capacity restricted)
Nominal output current (IN) 10 A (-25 °C ... 55 °C)
Derating 55 °C ... 70 °C (2.5%/K)
Connection in parallel Yes, for redundancy and increased capacity
Connection in series yes
Feedback voltage resistance 25 V DC
Protection against overvoltage at the output (OVP) < 25 V DC
Max. capacitive load unlimited
Active current limitation Approx. 12 A (in the event of a short-circuit)
Control deviation < 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 20 mVPP
Output power 120 W
Typical response time < 1 s
Peak switching voltages nominal load < 70 mVPP
Maximum power dissipation in no-load condition 1.1 W
Power loss nominal load max. 18 W

General

Net weight 0.6 kg
Operating voltage display Green LED
Efficiency > 86 % (for 230 V AC and nominal values)
Insulation voltage input/output 4 kV AC (type test)
2 kV AC (routine test)
Insulation voltage input / PE 2 kV AC (type test)
2 kV AC (routine test)
Insulation voltage output / PE 500 V DC (type test)
Protection class I (with PE connection)
Degree of protection IP20
MTBF (IEC 61709, SN 29500)
> 1871000 h (40 °C)
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions alignable: horizontally 0 mm, vertically 50 mm

Connection data, input

Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 9 mm
Screw thread M2,5

Connection data, output

Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 9 mm
Screw thread M2,5

EMC data

Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Low Voltage Directive Conformance with LV directive 2006/95/EC
Electrostatic discharge EN 61000-4-2
Contact discharge 6 kV (Test Level 3)
Discharge in air 8 kV (Test Level 3)
Electromagnetic HF field EN 61000-4-3
Frequency range 80 MHz ... 1 GHz
Test field strength 10 V/m
Frequency range 1 GHz ... 2 GHz
Test field strength 10 V/m
Frequency range 2 GHz ... 3 GHz
Test field strength 10 V/m
Comments Criterion A
Fast transients (burst) EN 61000-4-4
Input 4 kV (Test Level 4 - asymmetrical)
Output 4 kV (Test Level 4 - asymmetrical)
Signal 2 kV (Test Level 3 - asymmetrical)
Comments Criterion A
Surge voltage load (surge) EN 61000-4-5
Input 2 kV (Test Level 3 - symmetrical)
4 kV (Test Level 4 - asymmetrical)
Output 1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Comments Criterion A
Frequency range 0.15 MHz ... 80 MHz
Voltage 10 V (Test Level 3)
Comments Criterion A
Voltage dips EN 61000-4-11
No features entered