Power supply TRIO 1 phase 12VDC, 10A, 120W
Power supply TRIO 1 phase 12VDC, 10A, 120W
Power supply 12VDC with DIN rail mounting is robust, compact and efficient source, specialized on industrial automation systems. Input: 1x phase, output 12V DC, 10A. More
Manufacturer: PHOENIX CONTACT Code: 2866488
Power supply 12VDC with DIN rail mounting is robust, compact and efficient source, specialized on industrial automation systems. Input: 1x phase, output 12V DC, 10A. More
Manufacturer: PHOENIX CONTACT Code: 2866488
TRIO POWER power supplies with standard functionality
TRIO POWER is particularly suited to standard machine production, thanks to 1- and 3-phase versions up to 960 W. The wide-range input and the international approval package enable worldwide use.
The robust metal housing, the high electric strength, and the wide temperature range ensure a high level of power supply reliability.
- Use the third negative terminal block as a grounding terminal block and minimize installation costs
- Rugged design with metal housing and wide temperature range from -25 to +70°C
- Maximum operational reliability thanks to high MTBF (mean time between failures) of more than 500,000 hours and high dielectric strength of up to 300 V AC
- Compensation of voltage drops by means of output voltage that can be adjusted on the front
Dimensions
Width | 40 mm |
Height | 130 mm |
Depth | 115 mm |
Ambient conditions
Degree of protection | IP20 |
Ambient temperature (operation) | -25 °C ... 70 °C (> 55° C derating : 2.5%/K) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Climatic class | 3K3 (in acc. with EN 60721) |
Degree of pollution | 2 |
Input data
Nominal input voltage range | 100 V AC ... 240 V AC |
Input voltage range | 85 V AC ... 264 V AC (derating < 90 V AC: 2.5 % per Kelvin) |
Dielectric strength maximum | 300 V AC |
AC frequency range | 45 Hz ... 65 Hz |
Discharge current to PE | < 3.5 mA |
Current consumption | 1.7 A (120 V AC) |
0.9 A (230 V AC) | |
Nominal power consumption | 218.7 VA |
Inrush current | < 15 A |
Mains buffering time | > 20 ms (120 V AC) |
> 86 ms (230 V AC) | |
Recommended breaker for input protection | 6 A ... 16 A (Characteristics B, C, D, K) |
Power factor (cos phi) | 0.63 |
Type of protection | Transient surge protection |
Protective circuit/component | Varistor |
Output data
Nominal output voltage | 12 V DC ±1 % |
Setting range of the output voltage (USet) | 10 V DC ... 18 V DC (> 12 V DC, constant capacity restricted) |
Nominal output current (IN) | 10 A (-25 °C ... 55 °C) |
Derating | 55 °C ... 70 °C (2.5%/K) |
Connection in parallel | Yes, for redundancy and increased capacity |
Connection in series | yes |
Feedback voltage resistance | 25 V DC |
Protection against overvoltage at the output (OVP) | < 25 V DC |
Max. capacitive load | unlimited |
Active current limitation | Approx. 12 A (in the event of a short-circuit) |
Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
< 2 % (change in load, dynamic 10 % ... 90 %) | |
< 0.1 % (change in input voltage ±10 %) | |
Residual ripple | < 20 mVPP |
Output power | 120 W |
Typical response time | < 1 s |
Peak switching voltages nominal load | < 70 mVPP |
Maximum power dissipation in no-load condition | 1.1 W |
Power loss nominal load max. | 18 W |
General
Net weight | 0.6 kg |
Operating voltage display | Green LED |
Efficiency | > 86 % (for 230 V AC and nominal values) |
Insulation voltage input/output | 4 kV AC (type test) |
2 kV AC (routine test) | |
Insulation voltage input / PE | 2 kV AC (type test) |
2 kV AC (routine test) | |
Insulation voltage output / PE | 500 V DC (type test) |
Protection class | I (with PE connection) |
Degree of protection | IP20 |
MTBF (IEC 61709, SN 29500) | |
> 1871000 h (40 °C) | |
Mounting position | horizontal DIN rail NS 35, EN 60715 |
Assembly instructions | alignable: horizontally 0 mm, vertically 50 mm |
Connection data, input
Connection method | Screw connection |
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 14 |
Stripping length | 9 mm |
Screw thread | M2,5 |
Connection data, output
Connection method | Screw connection |
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 14 |
Stripping length | 9 mm |
Screw thread | M2,5 |
EMC data
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Low Voltage Directive | Conformance with LV directive 2006/95/EC |
Electrostatic discharge | EN 61000-4-2 |
Contact discharge | 6 kV (Test Level 3) |
Discharge in air | 8 kV (Test Level 3) |
Electromagnetic HF field | EN 61000-4-3 |
Frequency range | 80 MHz ... 1 GHz |
Test field strength | 10 V/m |
Frequency range | 1 GHz ... 2 GHz |
Test field strength | 10 V/m |
Frequency range | 2 GHz ... 3 GHz |
Test field strength | 10 V/m |
Comments | Criterion A |
Fast transients (burst) | EN 61000-4-4 |
Input | 4 kV (Test Level 4 - asymmetrical) |
Output | 4 kV (Test Level 4 - asymmetrical) |
Signal | 2 kV (Test Level 3 - asymmetrical) |
Comments | Criterion A |
Surge voltage load (surge) | EN 61000-4-5 |
Input | 2 kV (Test Level 3 - symmetrical) |
4 kV (Test Level 4 - asymmetrical) | |
Output | 1 kV (Test Level 2 - symmetrical) |
2 kV (Test Level 3 - asymmetrical) | |
Comments | Criterion A |
Frequency range | 0.15 MHz ... 80 MHz |
Voltage | 10 V (Test Level 3) |
Comments | Criterion A |
Voltage dips | EN 61000-4-11 |